Low Voltage Back
 

 

 

 

 
 
Home  >> Products >> Low Voltage >> Mini Circuit Breaker >> DZ48N-63 Series Miniature Circuit Breaker
 

 

 

 
1. Application
 
DZ48N-63 miniature circuit breaker is applicable to a line of AC 50Hz/60Hz, 230V in singlepole, 400V in double, three, four poles for protecting overload and short circuit, and rated cur-rent up to 63A. It can also be used for infrequent line conversion under the normal condition.Thebreaker is applicable to lighting distribution system in industrial enterprise, commercially district,high-rise building and dwelling house. It conforms with the standards of IEC60898.
 
 
2. Main Technical Parameter
 
Type DZ48N-63
Pole
1P 2P, 3P, 4P
Rated current (A)
6,10,16,20,25,32,40,50,63
Rated voltage(V)
230 400
Type of instantaneous release
C D C D
Rated short circuit breaking capacity Icn(KA)
1-40A: 6
50-63A: 4.5
4.5 1-40A: 6
50-63A: 4.5
4.5
Life (times) 1-32A
Electric life
4000
Mechanical life
6000
Operation frequency
240 times per hour
40-63A
Electric life
4000
Mechanical life
6000
Operation frequency
120 times per hour
 
 
3. Applicable conducting wire
 
Rated current(A) Nominal cross section of wire mm2
1-6A 1
10A 1.5
16,20A 2.5
25A 4
32A 6
40,50A 10
63A 16
 
4. The over-current protection property
 
Ambient Temperature Initial Status Test Current Expected Result Expected Result Note
30±2oC Cold position 1.13In t≥1h Non-release -
Carried out immediately after previous test 1.45In t<1h Release -
Cold position 2.55In 1s<t<60s
(In≤32A)
Release Current smoothly rises to specified value within 5s
Cold position 2.55In 1s<t<120s (In>32A) Release
-5~+40oC Cold position 3In t≥0.1s Non-release Type B
Cold position 5In t<0.1s Release Type B
Cold position 5In t≥0.1s Non-release Type C
Cold position 10In t<0.1s Release Type C
Cold position 10In t≥0.1s Non-release Type D
Cold position 20In t<0.1s Release Type D

 

 